• DocumentCode
    1558975
  • Title

    Hum noise performance of 6, 8, 10 conductor bundles for 1000 kV transmission lines at the Akagi test site: a comparative study with cage data

  • Author

    Tanabe, Kazuo

  • Author_Institution
    Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
  • Volume
    6
  • Issue
    4
  • fYear
    1991
  • fDate
    10/1/1991 12:00:00 AM
  • Firstpage
    1799
  • Lastpage
    1804
  • Abstract
    The hum noise performance of 6, 8, 10 conductor bundles (subconductor diameter: 3.84 cm) for 1000 kV transmission lines was measured at the Akagi test site and the results were compared with cage data. In general, hum noise levels calculated with cage data were higher than the long-term test results. It was found that the differences between calculated and measured levels were formulated with the maximum surface gradient. Based on this relationship a new prediction method for hum noise near AC transmission lines is proposed
  • Keywords
    acoustic noise; acoustic variables measurement; overhead line conductors; 1000 kV; Akagi test site; conductor bundles; hum noise performance; transmission lines; Acoustic noise; Circuit testing; Conductors; Corona; Noise level; Power transmission lines; Prediction methods; Transmission lines; Wires; Working environment noise;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.97724
  • Filename