DocumentCode
1558975
Title
Hum noise performance of 6, 8, 10 conductor bundles for 1000 kV transmission lines at the Akagi test site: a comparative study with cage data
Author
Tanabe, Kazuo
Author_Institution
Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
Volume
6
Issue
4
fYear
1991
fDate
10/1/1991 12:00:00 AM
Firstpage
1799
Lastpage
1804
Abstract
The hum noise performance of 6, 8, 10 conductor bundles (subconductor diameter: 3.84 cm) for 1000 kV transmission lines was measured at the Akagi test site and the results were compared with cage data. In general, hum noise levels calculated with cage data were higher than the long-term test results. It was found that the differences between calculated and measured levels were formulated with the maximum surface gradient. Based on this relationship a new prediction method for hum noise near AC transmission lines is proposed
Keywords
acoustic noise; acoustic variables measurement; overhead line conductors; 1000 kV; Akagi test site; conductor bundles; hum noise performance; transmission lines; Acoustic noise; Circuit testing; Conductors; Corona; Noise level; Power transmission lines; Prediction methods; Transmission lines; Wires; Working environment noise;