    Evaluation of ion counters using a facility to produce a steady state ion flow field

  • Author

    Suda, Tomotaka

  • Author_Institution
    Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
  • Volume
    6
  • Issue
    4
  • fYear
    1991
  • fDate
    10/1/1991 12:00:00 AM
  • Firstpage
    1805
  • Lastpage
    1811
  • Abstract
    A facility for producing a steady-state ion flow field (a low-speed wind tunnel) was developed for comparisons of aspirator-type ion counters. Ion densities achieved in this facility are comparable to those actually found near HVDC transmission lines, but are free from the accompanying large electric fields. This facility is useful for comparing different ion counters because it can supply constant ion density temporally within 9% variations. The flow-rate specifications of three ion counters were found to be inaccurate after the comparison of four ion counters using this facility
  • Keywords
    radiation detection and measurement; aspirator-type ion counters; ion counters; ion density; low-speed wind tunnel; steady state ion flow field; Corona; Counting circuits; Environmental factors; HVDC transmission; Instruments; Ion sources; Power transmission; Space charge; Steady-state; Wires;