• DocumentCode
    1564136
  • Title

    Distance relay over-reaching due to UPFC presence on second circuit of a double circuit line

  • Author

    Shateri, H. ; Jamali, Shahram

  • Author_Institution
    Centre of Excellence for Power Syst. Autom. & Oper., Iran Univ. of Sci. & Technol., Tehran
  • fYear
    2008
  • Firstpage
    783
  • Lastpage
    788
  • Abstract
    This paper discusses the distance relay over-reaching in the presence of unified power flow controller (UPFC), one of flexible alternating current transmission system (FACTS) devices, on the far end of the second circuit of a double circuit transmission line. This is done by presenting the measured impedance at the relaying point and the ideal tripping characteristic. The measured impedance at relaying point is greatly influenced in the presence of UPFC on the protected line or even in the case of UPFC presence on the far end of the second circuit. The measured impedance depends on many factors including power system structural conditions, the pre-fault loading, the ground fault resistance, and UPFC structural and controlling parameters.
  • Keywords
    earthing; fault diagnosis; flexible AC transmission systems; load flow control; FACTS devices; UPFC presence; circuit transmission line; distance relay over-reaching; flexible alternating current transmission system; ground fault resistance; power system structural conditions; pre-fault loading; unified power flow controller; Distance protection; FACTS devices; Fault resistance; Measured impedance; UPFC;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Power Electronics, Machines and Drives, 2008. PEMD 2008. 4th IET Conference on
  • Conference_Location
    York
  • ISSN
    0537-9989
  • Print_ISBN
    978-0-86341-900-3
  • Type

    conf

  • Filename
    4528945