• DocumentCode
    1573403
  • Title

    Harmonic domain characterization of the resonant interaction between generator and transmission line

  • Author

    Ramirez, Abner ; Semlyen, Adam ; Iravani, Reza

  • Author_Institution
    Toronto Univ., Ont., Canada
  • fYear
    2005
  • Abstract
    Summary form only given. It is known that an untransposed open-ended line causes a negative sequence component in the current and the generator reacts through third and higher harmonic voltages. The currents and voltages can be greatly amplified by resonance to any of these harmonics. The phenomenon of machine-line interaction has traditionally been explained as a sequence of interactive events between the line and the machine. This paper presents a unified non-iterative mathematical representation of this interaction. The analysis is formulated in the harmonic domain abc-frame to detect resonance conditions and for the assessment of their stability.
  • Keywords
    electric generators; harmonic analysis; power transmission lines; generators; harmonic domain abc-frame; harmonic domain characterization; harmonic voltages; machine-line interaction; negative sequence component; resonance condition detection; resonant interaction; transmission line; unified noniterative mathematical representation; untransposed open-ended line; Character generation; Harmonic analysis; Resonance; Stability analysis; Transmission lines; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society General Meeting, 2005. IEEE
  • Print_ISBN
    0-7803-9157-8
  • Type

    conf

  • DOI
    10.1109/PES.2005.1489231
  • Filename