Abstract
Tests conducted at a Bellcore thermal test facility demonstrate that the temperature in a typical 12-ft3 unpowered telecommunications power supply cabinet, with 3 inch thermal insulation and a 20 gallon water plenum and thermosiphon, can be held to between 30 and 80°F. The upper limit of 80°F was not exceeded even after a week of sunny days and peak outdoor temperatures approaching 95°F. In wintertime tests, water temperature did not go below 32°F, and the air temperature inside the cabinet did not go much below 30°F. There was enough water to prevent complete freezing. These measured results tracked well with predicted inside temperatures determined using a previously developed thermal model and support the use of the model to predict results in other climates and for other cabinet parameters, such as size and amounts of insulation
Keywords
cooling; power supplies to apparatus; telecommunication equipment; testing; thermal analysis; thermal insulation; 30 to 80 degF; cooling; outdoor cabinets; power supplies to apparatus; telecommunications equipment; testing; thermal analysis; thermal insulation; thermal model; thermal test facility; thermosiphon; water plenum; Cooling; Insulation testing; Passive optical networks; Phase change materials; Predictive models; Solar heating; Temperature control; Test facilities; Water heating; Wavelength division multiplexing;
fLanguage
English
Publisher
ieee
Conference_Titel
Telecommunications Energy Conference, 1992. INTELEC '92., 14th International
Conference_Location
Washington, DC
Print_ISBN
0-7803-0779-8
Type
conf
DOI
10.1109/INTLEC.1992.268436
Filename
268436
Link To Document