DC voltage limit compliance in voltage-source converter based multi-terminal HVDC
Author
Lu, Weixing ; Ooi, Boon Teck
Author_Institution
CYME Int. T&D, Que., Canada
fYear
2005
Firstpage
1322
Abstract
By adjusting Vref, the voltage reference setting of the DC voltage regulator or the power reference settings Pisp of the remaining converter stations, the steady-state DC bus voltages of the voltage-source converter based multi-terminal HVDC system can be made to comply with voltage limits. When any one of the converter stations is lost, over-voltage can destroy a converter station within a fraction of a second. As there is no time to reset the settings, the references must be determined in the very beginning to anticipate the accidental loss of a converter. The paper shows how the well-known voltage sensitivity method and the Lagrange multiplier method are adapted successfully to determine the reference settings for pre- and post-fault conditions.
Keywords
HVDC power convertors; overvoltage; voltage regulators; DC voltage limit compliance; Lagrange multiplier method; converter stations; fault conditions; multiterminal HVDC system; steady-state DC bus voltages; voltage reference setting; voltage sensitivity method; voltage-source converter; Cities and towns; Converters; HVDC transmission; Insulated gate bipolar transistors; Lagrangian functions; Load flow; Power conversion; Regulators; Steady-state; Voltage;