    DC voltage limit compliance in voltage-source converter based multi-terminal HVDC

  • Author

    Lu, Weixing ; Ooi, Boon Teck

  • Author_Institution
    CYME Int. T&D, Que., Canada
  • fYear
    2005
  • Firstpage
    1322
  • Abstract
    By adjusting Vref, the voltage reference setting of the DC voltage regulator or the power reference settings Pisp of the remaining converter stations, the steady-state DC bus voltages of the voltage-source converter based multi-terminal HVDC system can be made to comply with voltage limits. When any one of the converter stations is lost, over-voltage can destroy a converter station within a fraction of a second. As there is no time to reset the settings, the references must be determined in the very beginning to anticipate the accidental loss of a converter. The paper shows how the well-known voltage sensitivity method and the Lagrange multiplier method are adapted successfully to determine the reference settings for pre- and post-fault conditions.
  • Keywords
    HVDC power convertors; overvoltage; voltage regulators; DC voltage limit compliance; Lagrange multiplier method; converter stations; fault conditions; multiterminal HVDC system; steady-state DC bus voltages; voltage reference setting; voltage sensitivity method; voltage-source converter; Cities and towns; Converters; HVDC transmission; Insulated gate bipolar transistors; Lagrangian functions; Load flow; Power conversion; Regulators; Steady-state; Voltage;