DocumentCode :
1578920
Title :
Power system stabilizer with synthesized speed deviation signal
Author :
Hu, Xiaochen ; Sun, Yuanzhang ; Zhang, Jianyun
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
fYear :
2005
Firstpage :
1579
Abstract :
To completely avoid the temporary depression in generator terminal voltage during rapid governor actions, this paper uses synthesized speed deviation signal obtained by means of phasor measurement as PSS input. Low-pass differential filter and discrete compensation block are designed to attenuate noises and provide phase leading respectively. The effectiveness of PSS with the proposed stabilizing signal is verified in a simulation example of a single machine - infinite bus system after subjected to different disturbances including voltage step, governor action and three-phase short circuit fault. Both hydraulic and thermal units are considered.
Keywords :
low-pass filters; phase measurement; power filters; power system stability; discrete compensation block; governor actions; low-pass differential filter; phasor measurement; power system stabilizer; single machine - infinite bus system; synthesized speed deviation signal; temporary depression; terminal voltage; three-phase short circuit fault; Circuit noise; Circuit simulation; Low pass filters; Phase noise; Power system measurements; Power systems; Signal generators; Signal synthesis; Velocity measurement; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Society General Meeting, 2005. IEEE
Print_ISBN :
0-7803-9157-8
Type :
conf
DOI :
10.1109/PES.2005.1489447