DocumentCode
1584288
Title
The effect of inserting two clean discs in a polluted 275 kV AC string: an experimental investigation
Author
Kleinhans, K.D. ; Holtzhausen, J.P. ; Vosloo, W.L.
Author_Institution
Stellenbosch Univ., South Africa
Volume
4
fYear
1999
fDate
6/21/1905 12:00:00 AM
Firstpage
168
Abstract
This paper investigates the effect of a nonuniform distribution of a conductive surface layer along the length of a 275 kV cap and pin insulator string. The worst case is when one or two clean discs are inserted in a polluted string. A high electric field then exists across the clean discs, distorting the field to such an extent that localised flashover occurs across the clean discs
Keywords
insulator contamination; 275 kV; cap and pin insulator string; clean discs insertion; conductive surface layer; electric field distortion; high electric field; localised flashover; nonuniform distribution; polluted AC insulator string;
fLanguage
English
Publisher
iet
Conference_Titel
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location
London
ISSN
0537-9989
Print_ISBN
0-85296-719-5
Type
conf
DOI
10.1049/cp:19990819
Filename
821247
Link To Document