• DocumentCode
    1584288
  • Title

    The effect of inserting two clean discs in a polluted 275 kV AC string: an experimental investigation

  • Author

    Kleinhans, K.D. ; Holtzhausen, J.P. ; Vosloo, W.L.

  • Author_Institution
    Stellenbosch Univ., South Africa
  • Volume
    4
  • fYear
    1999
  • fDate
    6/21/1905 12:00:00 AM
  • Firstpage
    168
  • Abstract
    This paper investigates the effect of a nonuniform distribution of a conductive surface layer along the length of a 275 kV cap and pin insulator string. The worst case is when one or two clean discs are inserted in a polluted string. A high electric field then exists across the clean discs, distorting the field to such an extent that localised flashover occurs across the clean discs
  • Keywords
    insulator contamination; 275 kV; cap and pin insulator string; clean discs insertion; conductive surface layer; electric field distortion; high electric field; localised flashover; nonuniform distribution; polluted AC insulator string;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
  • Conference_Location
    London
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-719-5
  • Type

    conf

  • DOI
    10.1049/cp:19990819
  • Filename
    821247