• DocumentCode
    1584803
  • Title

    Synthetic measures of increasing flashover voltage for heavy contaminated insulators

  • Author

    Zhou, Wenjun ; Chen, Qingheng

  • Author_Institution
    Wuhan Univ. of Hydraulic & Electr. Eng., China
  • Volume
    4
  • fYear
    1999
  • fDate
    6/21/1905 12:00:00 AM
  • Firstpage
    269
  • Abstract
    Flashover voltage test results of artificially polluted insulators with 0.2 mg/cm2, 0.3 mg/cm2 and 2 mg/cm2 kaolin on 110 kV and 220 kV porcelain insulators, room temperature vulcanizing silicon rubber coating (RTV coating) and silicon rubber sheds put to porcelain insulators are presented in this paper. Using RTV coating combined with silicon rubber sheds to insulators has an effective performance to avoid contamination flashover and wetted flashover for heavy polluted area
  • Keywords
    insulator contamination; 110 kV; 220 kV; RTV coating; artificially polluted insulators; flashover voltage; heavy contaminated insulators; heavy polluted area; porcelain insulators; room temperature vulcanizing silicon rubber coating; silicon rubber sheds; wetted flashover;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
  • Conference_Location
    London
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-719-5
  • Type

    conf

  • DOI
    10.1049/cp:19990844
  • Filename
    821272