DocumentCode :
1585754
Title :
Research on the recovery fresh air heat pump units applications in the cold and serious cold regions
Author :
Chen Aoxue ; Ran Chunyu ; Liu Hailong
Author_Institution :
School of Municipal & Environmental Engineering, Jilin Institute of Architectural and Civil Engineer, Changchun, China
fYear :
2012
Firstpage :
1
Lastpage :
5
Abstract :
In order to solve the air-source heat pump can not work well in the cold and serious cold regions. This article carries on the theory and experimental study to the recovery fresh air heat pump units, with the recycled exhaust heat to heat fresh air, has mastered the system operation characteristics and the actual operating results. The experimental results show that the indexes meet the needs of load for heating in winter. The coefficient of performance (COP) is in the value of more than 3.80, and the heat recovery efficiency is up to 82%, which is prolonging the heat pump units and the fresh air units running in the period of heating, maintaining well Indoor Air Quality(IAQ) for a long time.
Keywords :
heat recovery efficiency; the coefficient of performance(COP); the cold and severe cold regions; the recovery fresh air heat pump units;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
World Automation Congress (WAC), 2012
Conference_Location :
Puerto Vallarta, Mexico
ISSN :
2154-4824
Print_ISBN :
978-1-4673-4497-5
Type :
conf
Filename :
6321500
Link To Document :
بازگشت