DocumentCode :
1586634
Title :
On selection of supplementary input signals for STATCOM to damp inter-area oscillations in power systems
Author :
Farsangi, Malihe M. ; Song, Yong Hua ; Lee, Kwang Y.
Author_Institution :
Kerman Univ., Iran
fYear :
2005
Firstpage :
3068
Abstract :
This paper proposes a method to select the supplementary input signal for systems equipped with static synchronous compensators (STATCOM) to damp inter-area mode(s). Input-output observability-controllability analysis, minimum singular value, right half plane zeros and relative gain array are used to assess the most appropriate supplementary input signal. The open-loop frequency of the system is shown to examine the sensitivity of the selected supplementary input signal to inter-area mode. The method is applied to select the input signal for a small power system equipped with a single STATCOM and for a large power system equipped with two STATCOMs.
Keywords :
power system stability; static VAr compensators; STATCOM; input-output observability-controllability analysis; open-loop frequency; power system damp interarea oscillations; relative gain array; right half plane zeros; static synchronous compensators; supplementary input signals selection; Automatic voltage control; Controllability; Damping; MIMO; Observability; Power system analysis computing; Power system interconnection; Power system stability; Power systems; Transmission line measurements;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Society General Meeting, 2005. IEEE
Print_ISBN :
0-7803-9157-8
Type :
conf
DOI :
10.1109/PES.2005.1489745