    Constant power control of grid connected inverters during unbalanced faults

  • Author

    Andrade, A. Ivan ; Blasco-Gimenez, Ramon ; Pena, R.S.

  • Author_Institution
    Univ. of Magallanes, Punta Arenas, Chile
  • fYear
    2013
  • Firstpage
    1
  • Lastpage
    7
  • Abstract
    This paper includes the theoretical analysis and experimental validation of a control strategy for the direct power and current control of grid-connected inverters. The studied control strategy allows for constant active and reactive power delivery during unsymmetrical faults and with supply voltage distortion, without the use of a PLL or FLL. It has been proven that only positive sequence current harmonics are necessary to deliver constant P and Q during unbalanced grid faults. The resulting stationary frame control has been experimentally validated during unbalanced voltage sags and swells.
  • Keywords
    electric current control; invertors; power control; power grids; power supply quality; constant active power delivery; constant power control; constant reactive power delivery; current control; direct power control; grid-connected inverters; positive sequence current harmonics; stationary frame control; supply voltage distortion; theoretical analysis; unbalanced grid faults; unbalanced voltage sags; unbalanced voltage swells; unsymmetrical faults; Harmonic analysis; Hysteresis; Inverters; Power control; Reactive power; Voltage control; Voltage fluctuations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics and Applications (EPE), 2013 15th European Conference on
  • Conference_Location
    Lille
  • Type

    conf

  • DOI
    10.1109/EPE.2013.6634681
  • Filename