    An inrush current elimination technique for line-interactive UPS systems during switching-in of an auxiliary load while feeding a main load

  • Author

    Bukhari, Syed Sabir Hussain ; Byung-il Kwon ; Lipo, Thomas A.

  • Author_Institution
    Hanyang Univ., Seoul, South Korea
  • fYear
    2014
  • fDate
    8-10 April 2014
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    Most industrial facilities involve use of various types of auxiliary loads in addition to a main sensitive load. Each of these loads are generally accompanied by load transformers. As these auxiliary loads are switched-in, their transformers also become energized. An inrush current often develops when the transformer is switched-in. This paper proposes an inrush current elimination technique for line-interactive UPS systems during the switching-in of auxiliary load transformers by utilizing a fast acting current regulated voltage source inverter. The proposed inrush current elimination technique is validated by simulation results.
  • Keywords
    invertors; transformers; uninterruptible power supplies; auxiliary load transformers; fast acting current regulated voltage source inverter; industrial facilities; inrush current elimination technique; line-interactive UPS systems; uninterruptible power supply; Inrush current; current regulated voltage source inverter; line-interactive UPS system;