DocumentCode :
1591674
Title :
Parallel control of the UPS inverters with frequency-dependent droop scheme
Author :
Chiang, S.J. ; Chang, J.M.
Author_Institution :
Dept. of Electr. Eng., Nat. Lien-Ho Inst. of Technol., Miao-Li, Taiwan
Volume :
2
fYear :
2001
fDate :
6/23/1905 12:00:00 AM
Firstpage :
957
Abstract :
This paper presents a control approach for paralleling the UPS inverters with no control interconnection. The reference voltage of the inverter is generated to simulate a reactor connected between the inverter and the load at the fundamental frequency. The intention is to control the real and reactive power sharing of the inverters with the Q-V and P-ω droop scheme without connection of a true transfer reactor. At the harmonic frequency the reference voltage turns to simulate a resistor, aiming that the load harmonic current can be shared equally and the voltage distortion is low. Two 1 kVA inverters are setup for demonstrating the effectiveness of the proposed approach
Keywords :
electric current control; invertors; power conversion harmonics; reactive power control; uninterruptible power supplies; 1 kVA; UPS inverters paralleling; current sharing control; frequency-dependent droop scheme; harmonic frequency; load harmonic current sharing; parallel control; reactive power sharing control; reactor simulation; real power sharing control; reference voltage generation; resistor simulation; voltage distortion; Automatic control; Circuit simulation; Frequency; Impedance; Inductors; Inverters; Power system harmonics; Power system interconnection; Uninterruptible power systems; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics Specialists Conference, 2001. PESC. 2001 IEEE 32nd Annual
Conference_Location :
Vancouver, BC
ISSN :
0275-9306
Print_ISBN :
0-7803-7067-8
Type :
conf
DOI :
10.1109/PESC.2001.954243
Filename :
954243
Link To Document :