• DocumentCode
    1591939
  • Title

    The study on measuring point selection of transformer vibration monitoring

  • Author

    Yuying, Shao ; Hong, Guan ; Yu, Zhang ; Zhijian, Jin ; Zhushi, Rao

  • Author_Institution
    Inst. of Technol. & Manage., SMEPC, Shanghai, China
  • Volume
    4
  • fYear
    2011
  • Firstpage
    241
  • Lastpage
    246
  • Abstract
    The selection of measuring points is an important problem for the vibration monitoring of transformers. The paper analyses the corresponding selecting principles. A series of experiments were conducted in one 220kV transformer with fixed-frequency variable current. The experimental results showed that the measuring points should be placed on the base of windings and the side wall of the tank. Another experiment was conducted with variable-frequency fixed-current. The results showed that different exciting frequency was important for choosing measuring points. Finally, three selecting principles were summarized.
  • Keywords
    condition monitoring; power transformers; vibrations; fixed-frequency variable current; measuring point selection; transformer vibration monitoring; variable-frequency fixed-current; voltage 220 kV; windings; Accelerometers; Current measurement; Frequency measurement; Oil insulation; Vibration measurement; Vibrations; Windings; measuring point; transformer; vibration;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electronic Measurement & Instruments (ICEMI), 2011 10th International Conference on
  • Conference_Location
    Chengdu
  • Print_ISBN
    978-1-4244-8158-3
  • Type

    conf

  • DOI
    10.1109/ICEMI.2011.6037987
  • Filename
    6037987