Title :
Snubber design for transformer protection
Author :
Sutherland, Peter E. ; Valdes, Marcelo E.
Author_Institution :
GE Energy, Schenectady, NY, USA
Abstract :
Historically, failures of distribution transformers due to transient overvoltage phenomena has led to the development of Resistor-Capacitor snubber circuits for the protection of the transformer and winding insulation. These transients are most often observed when dry-type transformers are close coupled to vacuum switching devices. Typically, snubber circuit design has been specific for the particular application, and complex engineering studies were required. However, the design of a snubber circuit itself may be performed without these detailed studies. If snubber studies are required, the procedures for system modeling and simulation are explained in a step by step manner.
Keywords :
power system transients; power transformer insulation; power transformer protection; snubbers; transformer windings; distribution transformers; dry-type transformers; resistor-capacitor snubber circuits; snubber circuit design; transformer protection; transient overvoltage; vacuum switching devices; winding insulation; Capacitors; Circuit faults; Power cables; Power transformer insulation; Resistors; Snubbers; Transient analysis; Circuit breakers; Electromagnetic transients; Equipment failure; Industrial power systems; Power distribution; Power system transients; Power transformers; Snubbers; Time-domain analysis;
Conference_Titel :
Petroleum and Chemical Industry Technical Conference (PCIC), 2014 IEEE
Conference_Location :
San Francisco, CA
Print_ISBN :
978-1-4799-3054-8
DOI :
10.1109/PCICon.2014.6961900