Title :
Oilfield electric power distribution
Author :
Durham, Robert A. ; Brinner, Thomas R.
Author_Institution :
THEWAY Labs., Bixby, OK, USA
Abstract :
The uniqueness of power system designs for oilfield distribution is seldom acknowledged or addressed. Utilities provide construction typical of either commercial or rural applications. Oilfields commonly have large concentrated loads separated by thousands of feet. To minimize line losses, medium voltage power is distributed and stepped-down at the point of use. In addition to common load flow analysis and protection coordination, transformers, surge arresters and grounding connections are important considerations for reliable production operations. Recloser settings typical for residential distribution cause major damage to submersible pumps. In remote areas where long neutral wires are necessary solidly grounded power contributes to equipment failure, but is nevertheless necessary for safety in surface equipment. The corner-grounded delta connection eliminates the neutral wire and is often used by rural utilities, despite its dangers. High-voltage three-wire construction can cause ferroresonance. Grounding influences the effectiveness of lightning and switching surge protection.
Keywords :
earthing; lightning protection; load flow; petroleum industry; power distribution protection; surge protection; concentrated loads; corner-grounded delta connection; equipment failure; ferroresonance; grounding connections; high-voltage three-wire construction; lightning protection; line losses; load flow analysis; medium voltage power; neutral wires; oilfield distribution; power system designs; protection coordination; recloser settings; rural utilities; submersible pumps; surge arresters; switching surge protection; transformers; Conductors; Grounding; Oil insulation; Surge protection; Windings; Wires; ESP; Power quality; SPD; TVSS; dirty power; electric submersible pumps; ground fault current; grounding; reactive power compensation; surge arresters; surge protection devices; transient voltage surge suppressors; ungrounded power; voltage impulses; voltage sag; voltage swell; wellhead grounding;
Conference_Titel :
Petroleum and Chemical Industry Technical Conference (PCIC), 2014 IEEE
Conference_Location :
San Francisco, CA
Print_ISBN :
978-1-4799-3054-8
DOI :
10.1109/PCICon.2014.6961908