    Analysis of asymmetrical short circuits downstream of 12 pulse diode rectifier fed by double three phase synchronous machines

  • Author

    Castellan, S. ; Tessarolo, Alberto ; Bortolozzi, M. ; Mezzarobba, M.

  • Author_Institution
    Univ. of Trieste, Trieste, Italy
  • fYear
    2014
  • fDate
    8-10 April 2014
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    DC power generation for MVDC grids is in the easiest way realized by a cascade connection of a synchronous generator and a diode rectifier. Due to large peak fault currents, including oscillating transient components, it is important to know in depth the short circuit behaviour of diode rectifiers, mainly during the first moments after the fault. This is helpful to be able to perform a suitable sizing of the system and its protections. In order to obtain an accurate estimation of the transient short circuit current, models for software simulation of 6-pulse and 12-pulse DC generator systems have been implemented. This paper shows the validation of such models by the comparison of simulation results with experimental tests.
  • Keywords
    rectifiers; smart power grids; synchronous generators; 12 pulse diode rectifier; 12-pulse DC generator system; DC power generation; MVDC grid; asymmetrical short circuit downstream analysis; double three phase synchronous machine; software simulation; synchronous generator; transient short circuit current; DC generators; asymmetrical short circuit; diode rectifiers; model validation; transient short circuit current;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Power Electronics, Machines and Drives (PEMD 2014), 7th IET International Conference on
  • Conference_Location
    Manchester
  • Electronic_ISBN
    978-1-84919-815-8
  • Type

    conf

  • DOI
    10.1049/cp.2014.0511
  • Filename
    6836985