DocumentCode
159297
Title
Alternate Arm Converter (AAC) operation under faulted AC-grid conditions
Author
Farr, E.M. ; Feldman, Ralph ; Watson, Alan J. ; Burgos, R.P. ; Clare, Jon C. ; Wheeler, Patrick W. ; Boroyevich, Dushan
Author_Institution
Machines & Control (PEMC) Res. Group, Univ. of Nottingham, Nottingham, UK
fYear
2014
fDate
8-10 April 2014
Firstpage
1
Lastpage
6
Abstract
This paper presents an AC-grid fault ride-through control strategy for a recently proposed modular multilevel Voltage Source Converter (VSC) named the Alternate Arm Converter (AAC). The primary purpose of the control strategy is to ensure that power balance can be maintained between the AC- and DC-terminals of the AAC. Therefore, the sub-module capacitor voltages can remain regulated. A set of simulation results for a line-line fault is presented.
Keywords
power convertors; power grids; power system control; power system faults; voltage control; AAC; AC grid fault ride through control; VSC; alternate arm converter; line-line fault; modular multilevel voltage source converter; power balance;