DocumentCode :
1594133
Title :
High real output power on-line UPS system with built-in reactive power compensation
Author :
Liang, T.J. ; Shyu, J.L. ; Chen, J.F.
Author_Institution :
Dept. of Electr. Eng., Nat. Cheng Kung Univ., Tainan, Taiwan
Volume :
3
fYear :
2001
fDate :
6/23/1905 12:00:00 AM
Firstpage :
1555
Abstract :
A circuit topology is proposed for single-phase online UPS systems. The proposed circuit incorporates a built-in bidirectional converter which provides power factor correction and active power filtering. The input stage, based on a bidirectional full-bridge converter, functions as a rectifier with unity power factor correction for normal AC line mode operation, and as an active power filter for outage mode operation. During input power failure, the DC/AC inverter output stage supplies real power from the battery bank to the critical load. Simultaneously, the bidirectional AC/DC converter functions as an active power filter, providing reactive power to the load. Thus, the real power capability is improved compared to conventional on-line UPS. Simulation of the proposed topology shows, for normal mode, a well regulated sinusoidal output voltage with minimum harmonic distortion for nonlinear loads, near-unity power factor and low-harmonic current for AC line. For outage mode, simulation shows a sinusoidal output voltage with low total harmonic distortion and a near-unity output power factor with a high utilization factor. Simulation results confirm the feasibility and features of the proposed UPS scheme
Keywords :
AC-DC power convertors; DC-AC power convertors; active filters; bridge circuits; compensation; harmonic distortion; invertors; power factor correction; power system harmonics; reactive power; uninterruptible power supplies; DC/AC inverter output stage; active power filter; active power filtering; battery bank; bidirectional AC/DC converter; bidirectional converter; bidirectional full-bridge converter; circuit topology; critical load; input power failure; input stage; low total harmonic distortion; low-harmonic current; minimum harmonic distortion; near-unity output power factor; near-unity power factor; nonlinear loads; normal AC line mode operation; outage mode; outage mode operation; power factor correction; reactive power; real power capability; rectifier; regulated sinusoidal output voltage; single-phase on-line UPS systems; sinusoidal output voltage; unity power factor correction; Active filters; Batteries; Circuit topology; Inverters; Power factor correction; Power generation; Power supplies; Reactive power; Rectifiers; Uninterruptible power systems;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics Specialists Conference, 2001. PESC. 2001 IEEE 32nd Annual
Conference_Location :
Vancouver, BC
ISSN :
0275-9306
Print_ISBN :
0-7803-7067-8
Type :
conf
DOI :
10.1109/PESC.2001.954340
Filename :
954340
Link To Document :
بازگشت