Title :
X-wax formation in transformer liquid dielectrics
Author :
Asokan, T. ; Bandaru, S.
Author_Institution :
GE India Technol. Center, India
Abstract :
Transformer wax (x-wax) formation in dielectric oil under electric stress is demonstrated in the laboratory scale. The x-wax is found to be insoluble and influences the oil-impedance characteristics significantly. The variation of oil-impedance as a function of electric stress exposure time revealed a unique transition in the oil-impedance. Initially, the impedance decreases with electric stress exposure time and at a threshold time the impedance increases. The transition point of impedance is attributed to the x-wax formation. These results are substantiated with the FTIR and microscopic analysis of the oil samples. The effect of temperature and moisture on the x-wax formation is studied. Besides, the study is extended to understand the role of copper and uncured resin on x-wax formation. The temperature is found to have more influence on the x-wax formation compared to moisture, copper and uncured resins.
Keywords :
dielectric liquids; power transformer insulation; power transformer testing; resins; transformer oil; FTIR; dielectric oil; electric stress; microscopic analysis; oil-impedance characteristics; resin; transformer liquid dielectrics; transformer wax; x-wax formation; Copper; Dielectric liquids; Impedance; Laboratories; Moisture; Oil insulation; Petroleum; Resins; Stress; Temperature;
Conference_Titel :
Dielectric Liquids, 2005. ICDL 2005. 2005 IEEE International Conference on
Print_ISBN :
0-7803-8954-9
DOI :
10.1109/ICDL.2005.1490110