  • Abstract
    Auxiliary DC systems that have considerable capacitance to ground, and that have balanced voltages between the DC polarities and ground, are at risk for false operation of switched DC loads. This can happen if an unintended ground develops at the critical points in the DC system. The sources of these large capacitances were investigated, as well as the vulnerability of sensitive interposing relay to false operation due to the unintended ground. An Electromagnetic Transient Program (EMTP/ATP) based simulation was performed to check the influence of the DC system and interposing relay parameters on the possibility of false operation. Means to eliminate the false operation are discussed.
  • Keywords
    EMTP; capacitance; power system protection; relays; EMTP-ATP based simulation; Electromagnetic Transient Program; auxiliary DC system capacitance; relay protection operation; switched DC load; Cables; Capacitance measurement; Control systems; Foot; Length measurement; Protective relaying; Rails; Substations; System testing; Wires; DC auxiliary system grounding; DC system capacitance; simulation of DC auxiliary system;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power & Energy Society General Meeting, 2009. PES '09. IEEE
  • Conference_Location
    Calgary, AB
  • ISSN
    1944-9925
  • Print_ISBN
    978-1-4244-4241-6
  • Type

    conf

  • DOI
    10.1109/PES.2009.5275949
  • Filename
    5275949