• DocumentCode
    1596355
  • Title

    Determination of the air-core reactance of transformers by analytical formulae for different topological configurations and its comparison with an electromagnetic 3D approach

  • Author

    Rioual, Michel ; Guillot, Yves ; Crepy, Cyrille

  • Author_Institution
    R&D Div., Electricite De France, Clamart, France
  • fYear
    2009
  • Firstpage
    1
  • Lastpage
    8
  • Abstract
    This document describes the determination of the saturated inductance of a transformer, which is the slope of the saturation curve Phi(I) under highly saturated conditions. This parameter, which has a strong impact on the overvoltages when energizing a transformer, has been determined from analytic formulae for different transformer technologies. A comparison with the values derived from an electromagnetic 3D calculation is also given in this paper.
  • Keywords
    overvoltage; power transformers; air-core reactance; electromagnetic 3D approach; overvoltage impact; topological configuration; transformer energization; transformer inductance saturation; Electromagnetic analysis; Impedance; Inductance; Magnetic cores; Power transformers; Strontium; Surges; Transformer cores; Windings; Zirconium; Energization; air-core inductance; air-core reactance; core-type; inrush currents; power transformer; saturated inductance; shell-type;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power & Energy Society General Meeting, 2009. PES '09. IEEE
  • Conference_Location
    Calgary, AB
  • ISSN
    1944-9925
  • Print_ISBN
    978-1-4244-4241-6
  • Type

    conf

  • DOI
    10.1109/PES.2009.5275962
  • Filename
    5275962