• DocumentCode
    1597853
  • Title

    Modeling ramped test results on single stator bars

  • Author

    Bernier, Simon ; Amyot, Normand ; David, Eric ; Navarrete, Benedicto ; Provencher, Hèlène

  • Author_Institution
    Ecole de Technol. Super. (ETS), Montreal, QC, Canada
  • fYear
    2010
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    This paper reports ramp test results on aged and spare bars. The measurements were carried out up to a maximum voltage of 21 kV in laboratory. The laboratory aged bars were compared to the spare bars with respect to their test results. Both a linear model and a non-linear model were used to reproduce the experimental results. In the case of non-linear responses (snaking), a correlation was made with the presence of delamination.
  • Keywords
    delamination; machine testing; stators; aged bars; nonlinear model; ramped test results; single stator bars; spare bars; voltage 21 kV; Aging; Circuit testing; Copper; Current measurement; Electrical resistance measurement; Insulation; Laboratories; Noise measurement; Stator bars; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation (ISEI), Conference Record of the 2010 IEEE International Symposium on
  • Conference_Location
    San Diego, CA
  • ISSN
    1089-084X
  • Print_ISBN
    978-1-4244-6298-8
  • Type

    conf

  • DOI
    10.1109/ELINSL.2010.5549727
  • Filename
    5549727