Abstract :
The story on revising criteria of dissolved gases analysis (DGA) at KEPCO was introduced. Because of differences in operating environments, construction type, oil volume, and other factors, the interpretative criteria of DGA at KEPCO should be different from other standards such as IEC-60599, or Rogers and Doernenburg. We tried to improve efficiency of DGA by considering accumulated data during twenty-five years. To establish the most appropriate criteria, the DGA results were collected from healthy power transformers as well as transformers which have an incipient fault. The criteria were revised newly using cumulative distribution of concentration of 3,585 healthy power transformers. Although the criteria are revised strictly, work load doesn´t increase by controlling analysis interval and condition level.
Keywords :
fault diagnosis; power transformer insulation; transformer oil; KEPCO; Korea; dissolved gas analysis; fault diagnosis; oil insulation; oil-filled transformers; power transformers; Dissolved gas analysis; Electrical fault detection; Fault detection; Gas insulation; Gases; Oil insulation; Petroleum; Power generation; Power system reliability; Power transformers; Fault diagnosis; Maintenance; Oil insulation; Power transformers;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power & Energy Society General Meeting, 2009. PES '09. IEEE
Conference_Location :
Calgary, AB
ISSN :
1944-9925
Print_ISBN :
978-1-4244-4241-6
Type :
conf
DOI :
10.1109/PES.2009.5276023
Filename :
5276023
Link To Document :
بازگشت