Abstract
The conditions required for the formation of copper sulfide originating from the DBDS oil additive which was identified by Scattigio (Terna, Italy) in 2005 is: "sufficiently high copper temperature" and copper corrosion will appear. This paper describes the findings when a transformer allegedly failed by corrosive sulfur was inspected with regards to the presence of copper corrosion. Strong corrosive attacks were found and their relation to temperature was very evident.
Keywords
copper compounds; corrosion; sulphur compounds; transformer oil; DBDS induced corrosive sulfur formation; DBDS oil; DBDS oil additive; copper corrosion; copper sulfide; copper temperature; corrosive attacks; di-benzyl di-sulfide; Chemical compounds; Copper; Corrosion; Energy states; Equations; Inspection; Oil insulation; Petroleum; Power transformer insulation; Temperature measurement; Arrhenius Equation; Copper corrosion; DBDS; catalytic induced; component; copper passivator; distribution; trigger temperature;