DocumentCode :
1599460
Title :
On-line monitoring of transformer bushings using a new decentralized measurement system
Author :
Riendeau, S. ; Picher, P. ; Léonard, F. ; Gauvin, M. ; Bertrand, H.
Author_Institution :
Res. Inst. (IREQ), Hydro-Quebec, Varennes, QC, Canada
fYear :
2010
Firstpage :
1
Lastpage :
5
Abstract :
A new bushing insulation monitoring system based on decentralized measurements of the bushing-tap current is presented. The development of this decentralized system is driven by the need to reduce the implementation cost of bushing monitoring based on the comparison of specimens connected in parallel on the same electrical phase. GPS is used for time synchronization of the decentralized measurements. The phase and amplitude measurement accuracy specifications are respectively 0.01° and 0.1%. These specifications are required to allow monitoring of the insulation degradation as well as variations of the bushing capacitance and power/dissipation factor introduced by the fluctuation of the internal insulation temperature and ambient conditions (e.g. rain). Simulations of the new decentralized measurement system were performed to determine the detailed specifications. The system will be validated by comparing it with on-line measurements performed on nine 735/230-kV transmission transformers using a standard galvanic measurement system. These transformers are located in a substation with HVDC converters, which represents a challenging noisy environment for such accurate measurements.
Keywords :
Global Positioning System; HVDC power convertors; bushings; capacitance; power system measurement; power transformer insulation; substations; GPS; HVDC converter; bushing capacitance; bushing tap current; decentralized measurement system; galvanic measurement system; internal insulation temperature; power-dissipation factor; substation; time synchronization; transformer bushing insulation monitoring system; transmission transformer; voltage 230 V; voltage 735 V; Condition monitoring; Costs; Current measurement; Degradation; Global Positioning System; Insulators; Performance evaluation; Phase measurement; Power transformer insulation; Time measurement; GPS synchronization; bushing; insulation diagnostic; monitoring; power dissipation factor;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation (ISEI), Conference Record of the 2010 IEEE International Symposium on
Conference_Location :
San Diego, CA
ISSN :
1089-084X
Print_ISBN :
978-1-4244-6298-8
Type :
conf
DOI :
10.1109/ELINSL.2010.5549788
Filename :
5549788