• DocumentCode
    1600165
  • Title

    Test and study of 10kV XLPE power cables´ typical defects based on Oscillating Wave Test System

  • Author

    Zhijuan, Chen ; Gang, Liu ; Chengwei, Chen ; Guojun, Lu

  • Author_Institution
    Sch. of Electr. Power, South China Univ. of Technol., Guangzhou, China
  • fYear
    2010
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Based on the laboratory test carried out on 351m 10kV XLPE power cable in which there are some typical PD defects, the method of OWTS for detecting PD in XLPE cable and its accessories was introduced. The time domain characters of the OWTS signal is researched in order to distinguish the PD signal from the disturbance. The PD spectrum of q-m was analyzed. The way to locate the PD point was also introduced. The results of the research had proved that the reliability of the PD detection is improved using the method of OWTS.
  • Keywords
    XLPE insulation; partial discharge measurement; power cable insulation; time-domain analysis; OWTS signal; PD detection; XLPE power cables; cable PD defects; distance 351 m; oscillating wave test system; partial discharges measurements; time domain characters; voltage 10 kV; Cable insulation; Circuit testing; Dielectric losses; Inductors; Partial discharges; Power cables; Pressing; Switches; System testing; Voltage; cable accessories; fault location; oscillating wave; partial discharge; typical PD defects;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation (ISEI), Conference Record of the 2010 IEEE International Symposium on
  • Conference_Location
    San Diego, CA
  • ISSN
    1089-084X
  • Print_ISBN
    978-1-4244-6298-8
  • Type

    conf

  • DOI
    10.1109/ELINSL.2010.5549815
  • Filename
    5549815