DocumentCode
1601483
Title
Overvoltage spikes transmitted through distribution transformers due to MV spark-gap operation
Author
Sabiha, Nehmdoh A. ; Lehtonen, Matti
Author_Institution
Dept. of Electr. Eng., Aalto Univ., Espoo, Finland
fYear
2010
Firstpage
207
Lastpage
214
Abstract
Small distribution transformers are often protected with spark gaps. As the spark-gap ignites, an overvoltage is coupled to the secondary side due to the steep voltage change. This overvoltage can reach to the customer socket. In this paper, the breakdown of MV spark-gaps is first modeled under an impulse voltage superimposed on AC voltage. To study the overvoltage propagation to the low voltage side, an accurate and simplified high frequency transformer model is used. The model, MV spark-gap and LV network are combined in ATP/EMTP to study the overvoltage spike propagation. Finally, the low voltage surge arrester at the secondary terminals of the distribution transformer is investigated for overvoltage mitigation.
Keywords
arresters; high-frequency transformers; overvoltage protection; power transformer protection; spark gaps; AC voltage; ATP-EMTP; LV network; MV spark-gap operation; distribution transformers; high frequency transformer model; impulse voltage; low voltage surge arrester; overvoltage mitigation; overvoltage spike propagation; Breakdown voltage; EMTP; Frequency; Low voltage; Protection; Sockets; Spark gaps; Surges; Transformers; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Electric Power Quality and Supply Reliability Conference (PQ), 2010
Conference_Location
Kuressaare
Print_ISBN
978-1-4244-6978-9
Type
conf
DOI
10.1109/PQ.2010.5549996
Filename
5549996
Link To Document