• DocumentCode
    1601483
  • Title

    Overvoltage spikes transmitted through distribution transformers due to MV spark-gap operation

  • Author

    Sabiha, Nehmdoh A. ; Lehtonen, Matti

  • Author_Institution
    Dept. of Electr. Eng., Aalto Univ., Espoo, Finland
  • fYear
    2010
  • Firstpage
    207
  • Lastpage
    214
  • Abstract
    Small distribution transformers are often protected with spark gaps. As the spark-gap ignites, an overvoltage is coupled to the secondary side due to the steep voltage change. This overvoltage can reach to the customer socket. In this paper, the breakdown of MV spark-gaps is first modeled under an impulse voltage superimposed on AC voltage. To study the overvoltage propagation to the low voltage side, an accurate and simplified high frequency transformer model is used. The model, MV spark-gap and LV network are combined in ATP/EMTP to study the overvoltage spike propagation. Finally, the low voltage surge arrester at the secondary terminals of the distribution transformer is investigated for overvoltage mitigation.
  • Keywords
    arresters; high-frequency transformers; overvoltage protection; power transformer protection; spark gaps; AC voltage; ATP-EMTP; LV network; MV spark-gap operation; distribution transformers; high frequency transformer model; impulse voltage; low voltage surge arrester; overvoltage mitigation; overvoltage spike propagation; Breakdown voltage; EMTP; Frequency; Low voltage; Protection; Sockets; Spark gaps; Surges; Transformers; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Quality and Supply Reliability Conference (PQ), 2010
  • Conference_Location
    Kuressaare
  • Print_ISBN
    978-1-4244-6978-9
  • Type

    conf

  • DOI
    10.1109/PQ.2010.5549996
  • Filename
    5549996