DocumentCode :
1610838
Title :
Protection scheme considerations for common generator bus configurations used in cogeneration plants
Author :
Rifaat, Rasheek M.
Author_Institution :
Delta Catalytic Eng. & Construction Ltd., Calgary, Alta., Canada
fYear :
1993
fDate :
6/15/1905 12:00:00 AM
Firstpage :
1
Lastpage :
6
Abstract :
The author discusses the applications of protective relaying schemes in modern power cogeneration plants with common generator bus arrangements. Main protection system philosophy and scheme characteristics are considered. Emphasis is given to the attributes of common generator bus configurations. High resistance neutral grounding protection sensitivity and coordinate ability are addressed. Critical considerations are identified to be evaluated in the case of plants connected to multi-tap utility transmission lines.
Keywords :
cogeneration; electric generators; machine protection; cogeneration plants; common generator bus configurations; coordinate ability; high resistance neutral grounding; multi-tap utility transmission lines; protection system philosophy; protective relaying schemes; Circuit faults; Cogeneration; Control systems; Power generation; Power system protection; Protective relaying; Standby generators; Stators; Transformers; Turbines;