DocumentCode :
1611656
Title :
Locating fault using voltage sags profile for underground distribution system
Author :
Mokhlis, H. ; Li, H.Y. ; Bakar, A.H.A. ; Mohamad, Hasmaini
Author_Institution :
Dept. of Electr. Eng., Univ. of Malaya, Kuala Lumpur, Malaysia
fYear :
2010
Firstpage :
1
Lastpage :
7
Abstract :
This paper presents an alternative fault location algorithm to estimate short-circuit faults location in electrical distribution networks using only voltage sags data. The proposed algorithm uses voltage sags profile as a means to locate fault. The possible fault locations is estimated by incorporating the measured voltage sags magnitude and its corresponding phase angle into an equation of voltage sag as a function of fault distance. A ranking procedure is also introduced to rank possible fault locations due the same electrical distance. The uncertainty of fault resistance is also considered in this algorithm. The performance of the technique is presented by testing it using an actual underground distribution network. The simulation results indicated a possibility of practical implementation.
Keywords :
fault location; power distribution faults; power supply quality; underground distribution systems; electrical distance; fault distance function; phase angle; short-circuit fault location algorithm; underground electrical distribution networks; voltage sag equation; Databases; Electric variables measurement; PSCAD; Resistance; Fault location; distribution networks; phase shift; voltage magnitude;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power System Technology (POWERCON), 2010 International Conference on
Conference_Location :
Hangzhou
Print_ISBN :
978-1-4244-5938-4
Type :
conf
DOI :
10.1109/POWERCON.2010.5666450
Filename :
5666450
Link To Document :
بازگشت