DocumentCode
1611659
Title
System integrity protection and control based on synchronized measurements
Author
Skok, Srdjan ; Kirincic, Vedran ; Brnobic, Dalibor ; Cerina, Zdeslav ; Bulat, Hrvoje
Author_Institution
Fac. of Eng., Univ. of Rijeka, Rijeka, Croatia
fYear
2013
Firstpage
198
Lastpage
203
Abstract
The paper presents a control system solution based on synchronized phasor measurements for the urban area transmission system. Specificity of the analyzed system is a highly meshed overhead and cable sections network, with two city power plants, providing the city´s district heating and electricity supply. The mathematical model for static and dynamic analyses of various scenarios was build and verified using measurements from originally developed and deployed portable hand-held phasor measurement units. The control system architecture and functionalities as well as developed control actions algorithms are given, focusing on island operation of the issued transmission system, as the city power plants are capable to supply the critical consumers.
Keywords
SCADA systems; phasor measurement; power plants; power system control; power system protection; cable sections network; city power plants; control actions algorithms; control system solution; district heating; dynamic analysis; electricity supply; island operation; overhead network; phasor measurement units; static analysis; synchronized phasor measurements; system integrity protection; urban area transmission system; Control systems; Phasor measurement units; Power cables; Power measurement; Substations; Voltage measurement; Automated Control; Islanding; Power System Control; Synchronized Measurement; System Integrity Protection Scheme;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering, Energy and Electrical Drives (POWERENG), 2013 Fourth International Conference on
Conference_Location
Istanbul
ISSN
2155-5516
Type
conf
DOI
10.1109/PowerEng.2013.6635606
Filename
6635606
Link To Document