• DocumentCode
    1612698
  • Title

    A study on design review of the control performance of the air conditioning to prevent room pressure change troubles

  • Author

    Tanaka, Daiki ; Koike, Takamitsu ; Tanaka, Nobuhiro ; Miyake, Takayuki ; Tateno, Shigeyuki ; Matsuyama, Hisayoshi

  • Author_Institution
    Graduate Sch. of Inf., Production & Syst., Waseda Univ., Kitakyushu
  • fYear
    2006
  • Firstpage
    5573
  • Lastpage
    5578
  • Abstract
    It is very important to keep different pressure among rooms with different cleanness in pharmaceutical factories, semiconductor factories and so on. However, a trouble, that caused by the room pressure changes, is frequently detected at commissioning systems and results in significant losses of time and money. A method of design review, by use of a simulation, is proposed in this paper to prevent trouble of room pressure change. The commissioning test removes the causes of the trouble in the design stage. This paper notes simulation results of the air-conditioning systems. The simulator is made by MATLAB and SIMULINK. The developed method of this simulator is expounded by use of Base-model in which all kind of elements of air-conditioning components are included. When room pressure of the Base-model is controlled, the simulator measures room pressure change and flow rate change. The simulator can evaluate the systems beforehand only by design information. As an example of evaluation of the systems, an actual air-conditioning system, where the room pressure change trouble occurs, is verified. It adequately explains the cause and solution of this trouble
  • Keywords
    air conditioning; control system synthesis; digital simulation; mathematics computing; power engineering computing; production facilities; MATLAB; SIMULINK; air conditioning control performance; design review; flow rate change; room pressure change trouble; Air conditioning; Control systems; Ducts; Filters; MATLAB; Mathematical model; Pharmaceuticals; Pressure control; Production facilities; Transfer functions; Air conditioning; MATLAB; Room pressure trouble; SIMULINK; Simulation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    SICE-ICASE, 2006. International Joint Conference
  • Conference_Location
    Busan
  • Print_ISBN
    89-950038-4-7
  • Electronic_ISBN
    89-950038-5-5
  • Type

    conf

  • DOI
    10.1109/SICE.2006.315779
  • Filename
    4108780