Study of transformer resonant overvoltages caused by cable-transformer high-frequency interaction
Author
Gustavsen, Bjørn
Author_Institution
SINTEF Energy Research
fYear
2011
Firstpage
1
Lastpage
1
Abstract
Summary form only given. Power transformers can fail from dielectric stresses caused by electromagnetic transients. In this paper we focus on a special phenomenon where excessive overvoltages arise due to resonance. This situation can take place when a transformer on the high-voltage side is connected to a cable and the low-voltage side is unloaded. Very high overvoltages can then result on the low-voltage side from transient events that cause a weakly attenuated overvoltage on the cable with a dominant frequency matching a resonance peak in the transformer voltage ratio. Laboratory tests on a 11 kV/230 V distribution transformer show that a step voltage excitation on a 27-m cable produces a 24 p.u. overvoltage on the open low-voltage side. The voltage waveforms are accurately reproduced by a black-box model obtained from frequency sweep measurements. Simulations show that overvoltages as high as 43 p.u. could occur with the most unfavorable cable length. It is further shown that the following situations can lead to high overvoltages on an unloaded transformer low-voltage side: 1) ground fault initiation at the far cable end, 2) cable energization from a busbar with several other cables connected, and 3) cable energization from another cable of same length.
Keywords
busbars; dielectric properties; earthing; frequency measurement; overvoltage; power cables; power system transients; power transformer testing; black-box model; busbar; cable energization; cable-transformer high-frequency interaction; dielectric stress; distribution transformer; electromagnetic transient; frequency matching; frequency sweep measurement; ground fault; laboratory tests; power transformer; size 27 m; step voltage excitation; transformer high-voltage side; transformer resonant overvoltages; transformer voltage ratio; unloaded transformer low-voltage side; voltage 11 kV; voltage 230 V; voltage waveforms; weakly attenuated overvoltage; Frequency measurement; Laboratories; Power cables; Power transformers; Resonant frequency; Surges; Voltage measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Society General Meeting, 2011 IEEE
Conference_Location
San Diego, CA
ISSN
1944-9925
Print_ISBN
978-1-4577-1000-1
Electronic_ISBN
1944-9925
Type
conf
DOI
10.1109/PES.2011.6038890
Filename
6038890
Link To Document