DocumentCode :
1613517
Title :
Locating voltage sag source with impedance measurement
Author :
Shao, Zhenguo ; Peng, JinPing ; Kang, Jian
Author_Institution :
Coll. of Electr. Eng. & Autom., Fuzhou Univ., Fuzhou, China
fYear :
2010
Firstpage :
1
Lastpage :
6
Abstract :
Voltage sag is one of the major power quality problems that maybe result from networks fault and sudden increase of the load. It will result in abnormal operation or shutting down of device. Sag location is an important topic because power-quality trouble-shooting, diagnosis, mitigation policy could be constituted and mitigation measurement be carried out only after locating the voltage sag source accurately. A method based on the impedance measurement in dq0 coordinate system is proposed in this paper. Firstly, the three-phase voltage and current measured at the monitoring point are transformed by the orthogonal Park´s transformation. And then the certain character of obtained three-phase instantaneous impedance measurement is used to locate the sources of the voltage sags. Constant impedance load and induction-motor load are used in digital simulation respectively. The simulation results show that the method can locate the disturbance source whether symmetrical or asymmetrical happens.
Keywords :
electric current measurement; electric impedance measurement; fault diagnosis; induction motors; power supply quality; voltage measurement; current measurement; impedance measurement; induction motor; networks fault; power quality; voltage measurement; voltage sag source; Impedance; Impedance measurement; Integrated circuits; MATLAB; Variable speed drives; impedance measurement; induction-motor; location; voltage sag source;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power System Technology (POWERCON), 2010 International Conference on
Conference_Location :
Hangzhou
Print_ISBN :
978-1-4244-5938-4
Type :
conf
DOI :
10.1109/POWERCON.2010.5666557
Filename :
5666557
Link To Document :
بازگشت