• DocumentCode
    1613532
  • Title

    Development of condition evaluation for power transformer maintenance

  • Author

    Haema, J. ; Phadungthin, R.

  • Author_Institution
    Dept. of Electr. Eng. Technol., King Mongkut´s Univ. of Technol. North Bangkok, Bangkok, Thailand
  • fYear
    2013
  • Firstpage
    620
  • Lastpage
    623
  • Abstract
    The development of condition evaluation for power transformer maintenance are presented in this paper. The techniques consist of three types: electrical test, insulating oil test and visual inspection, which is considered by 21 test methods: Dissolved Gas Analysis, Load History, Power Factor, Thermo Scan, Oil Quality, Furan, General Condition, Bushing, Surge Arrester, Conservator Tank, Main Tank, Hot Line Oil Filter, Radiator and Cooling System, Transformer Control Cabinet, Neutral Ground Reactor (NGR), Protection Equipment, Regulating PT, OLTC Compartment, OLTC Control Cabinet, DGA of OLTC, and OLTC Oil Quality. The condition assessment for transformer is performed by the analysis of each method, indicated by scoring and weighting factor of each tests. This method with further development could be used to effectively plan the maintenance of power transformer.
  • Keywords
    chemical analysis; condition monitoring; cooling; maintenance engineering; on load tap changers; power transformer protection; transformer oil; DGA; NGR; OLTC compartment; OLTC control cabinet; OLTC oil quality; bushing; condition evaluation development; conservator tank; cooling system; dissolved gas analysis; electrical test; furan; general condition; hot line oil filter; insulating oil test; load history; main tank; neutral ground reactor; oil quality; power factor; power transformer maintenance; protection equipment; radiator; regulating PT; surge arrester; thermo scan; transformer condition assessment; transformer control cabinet; visual inspection; Color; Maintenance engineering; Oil insulation; Power transformer insulation; Reactive power; Testing; health index of power transformer; power transformer condition; power transformer maintenance;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering, Energy and Electrical Drives (POWERENG), 2013 Fourth International Conference on
  • Conference_Location
    Istanbul
  • ISSN
    2155-5516
  • Type

    conf

  • DOI
    10.1109/PowerEng.2013.6635680
  • Filename
    6635680