• DocumentCode
    1613698
  • Title

    Ageing studies on paper and oil to assess the condition of solid insulation used in power transformers

  • Author

    Thomas, P. ; Shukla, A.K. ; Raghuveer

  • Author_Institution
    Central Power Res. Inst., Bangalore, India
  • fYear
    2001
  • fDate
    6/23/1905 12:00:00 AM
  • Firstpage
    69
  • Lastpage
    72
  • Abstract
    The present study involves the ageing of insulation paper and oil samples at three different temperatures, i.e. 85 °C, 100 °C and 115 °C, for 1000 h in the laboratory. The deterioration in mechanical and electrical properties of paper as a result of ageing has been correlated with a fall in the degree of polymerization and a rise in furan content
  • Keywords
    ageing; condition monitoring; dielectric losses; electric breakdown; insulation testing; paper; polymerisation; power transformer insulation; power transformer testing; tensile strength; transformer oil; viscosity; 1000 h; 85 to 115 C; ageing; breakdown voltage; degree of polymerization; electrical properties; furan content; high performance liquid chromatography; insulation condition assessment; mechanical properties; oil insulation; paper insulation; power transformer insulation; tan delta measurement; tensile strength; Aging; Dielectrics and electrical insulation; Gases; Oil insulation; Organic materials; Petroleum; Polymers; Power transformer insulation; Power transformers; Solids;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Solid Dielectrics, 2001. ICSD '01. Proceedings of the 2001 IEEE 7th International Conference on
  • Conference_Location
    Eindhoven
  • Print_ISBN
    0-7803-6352-3
  • Type

    conf

  • DOI
    10.1109/ICSD.2001.955515
  • Filename
    955515