• DocumentCode
    1616611
  • Title

    Assessing aging of large transformers by furfural investigation

  • Author

    Shang, Y. ; Yang, L. ; Guo, Z.J. ; Yan, Z.

  • Author_Institution
    Dept. of Electr. Eng., Xi´´an Jiaotong Univ., China
  • fYear
    2001
  • fDate
    6/23/1905 12:00:00 AM
  • Firstpage
    272
  • Lastpage
    274
  • Abstract
    Chinese research work of assessing transformer aging via furfural analysis is introduced. Abnormal, normal and deferred aging conditions of paper insulation in transformers are put forward by means of statistical analysis of furfural in the field. It is recommended that relevant measurement information such as moisture, oxygen, as well as power, voltage, etc. is recorded. Increasing rate of furfural in oil is highly emphasized. However, more laboratory studies should be undertaken, in order to get closer to the mechanism of paper degradation
  • Keywords
    ageing; transformer oil; transformers; aging; furfural analysis; large transformers; paper degradation; paper insulation; Aging; Chemicals; Degradation; Hydrogen; Minerals; Oil insulation; Petroleum; Polymers; Power transformer insulation; Power transformers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Solid Dielectrics, 2001. ICSD '01. Proceedings of the 2001 IEEE 7th International Conference on
  • Conference_Location
    Eindhoven
  • Print_ISBN
    0-7803-6352-3
  • Type

    conf

  • DOI
    10.1109/ICSD.2001.955620
  • Filename
    955620