Abstract :
Accelerated electrical breakdown in ERIP (epoxy resin impregnated paper) condenser bushings has been investigated. Inter-foil breakdown of the grading foils, via electrical treeing, occurred over several 10s of hours when the applied electrical stress was ~6 times the normal working stress. The progress of inter-foil breakdown could be monitored using a simple capacitance measurement technique. The bushing breakdown times were reproducible and decreased with increasing temperature. Many bushings operate at temperatures in excess of 90°C and so the breakdown times would be expected to decrease further. However, the service life for bushings at service stress and service temperature is in excess of 40 years
Keywords :
bushings; capacitance; epoxy insulators; impregnated insulation; paper; power capacitors; trees (electrical); 36 kV; HV ERIP condenser bushings; accelerated ageing; capacitance; conducting paths; electrical treeing breakdown; epoxy resin impregnated paper; grading foils; inter-foil breakdown; service life; Aluminum; Breakdown voltage; Capacitance; Conductors; Electric breakdown; Epoxy resins; Insulators; Transformers; Trees - insulation; Wounds;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Solid Dielectrics, 2001. ICSD '01. Proceedings of the 2001 IEEE 7th International Conference on
Conference_Location :
Eindhoven
Print_ISBN :
0-7803-6352-3
Type :
conf
DOI :
10.1109/ICSD.2001.955642
Filename :
955642
Link To Document :
بازگشت