• DocumentCode
    1617264
  • Title

    Inter-foil electrical breakdown in high voltage ERIP condenser bushings

  • Author

    Champion, J.V. ; Dodd, S.J.

  • Author_Institution
    London Guildhall Univ., UK
  • fYear
    2001
  • fDate
    6/23/1905 12:00:00 AM
  • Firstpage
    329
  • Lastpage
    332
  • Abstract
    Accelerated electrical breakdown in ERIP (epoxy resin impregnated paper) condenser bushings has been investigated. Inter-foil breakdown of the grading foils, via electrical treeing, occurred over several 10s of hours when the applied electrical stress was ~6 times the normal working stress. The progress of inter-foil breakdown could be monitored using a simple capacitance measurement technique. The bushing breakdown times were reproducible and decreased with increasing temperature. Many bushings operate at temperatures in excess of 90°C and so the breakdown times would be expected to decrease further. However, the service life for bushings at service stress and service temperature is in excess of 40 years
  • Keywords
    bushings; capacitance; epoxy insulators; impregnated insulation; paper; power capacitors; trees (electrical); 36 kV; HV ERIP condenser bushings; accelerated ageing; capacitance; conducting paths; electrical treeing breakdown; epoxy resin impregnated paper; grading foils; inter-foil breakdown; service life; Aluminum; Breakdown voltage; Capacitance; Conductors; Electric breakdown; Epoxy resins; Insulators; Transformers; Trees - insulation; Wounds;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Solid Dielectrics, 2001. ICSD '01. Proceedings of the 2001 IEEE 7th International Conference on
  • Conference_Location
    Eindhoven
  • Print_ISBN
    0-7803-6352-3
  • Type

    conf

  • DOI
    10.1109/ICSD.2001.955642
  • Filename
    955642