Title :
Partial discharge on-line monitoring in switchgears and bus ducts
Author :
Berler, Z. ; Blokhintsev, I. ; Golubev, A.
Author_Institution :
Cutler-Hammer Predictive Diagnostics, Minnetonka, MN, USA
fDate :
6/23/1905 12:00:00 AM
Abstract :
The paper describes the positive practical experience in PD measurements in switchgears and bus ducts using a portable computerized partial discharge analyzer UPDA. On-line PD technology proved to be a fast, convenient and cost effective non-invasive tool in revealing numerous places of worsened insulation and other defects (bad contacts, loose insulators, insufficient distances between HV bus and secondary wiring, etc.) in switchgears and bus ducts of medium voltages. This technology was successfully applied to numerous objects in electric utilities, industrial customers and nuclear power plants
Keywords :
busbars; computerised monitoring; current transformers; insulation testing; partial discharge measurement; switchgear insulation; HV breaker assemblies; PD measurements; PD on-line monitoring; bus ducts; current transformer; portable computerized partial discharge analyzer; secondary circuit; switchgears; Computerized monitoring; Costs; Ducts; Insulation; Medium voltage; Partial discharge measurement; Partial discharges; Portable computers; Power industry; Wiring;
Conference_Titel :
Solid Dielectrics, 2001. ICSD '01. Proceedings of the 2001 IEEE 7th International Conference on
Conference_Location :
Eindhoven
Print_ISBN :
0-7803-6352-3
DOI :
10.1109/ICSD.2001.955654