Criteria for diagnostic evaluation of water treed XLPE cables
Author :
Hvidsten, Sverre ; Ildstad, Erling
Author_Institution :
SINTEF Energy Res., Norway
fDate :
6/23/1905 12:00:00 AM
Abstract :
To detect cables with water trees bridging the insulation, it is necessary to perform measurements during application of test voltage. This is automatically obtained by the AC frequency domain methods. When using the DC time domain methods the polarisation current should be measured at a sufficient high DC test voltage. The good correlation between the degree of non-linearity and the cable condition, indicate that the test voltage can be limited to U0. To base the diagnostic evaluation on the S values facilitates comparison of results from different diagnostic methods. In addition such transformation makes it easier to compare results from time domain measurements performed at several voltages, different types and lengths of cables
Keywords :
XLPE insulation; dielectric measurement; discharges (electric); failure analysis; insulation testing; power cable insulation; power cable testing; AC frequency domain methods; DC time domain methods; correlation; diagnostic evaluation; dielectric response; insulation; polarisation current; service aged XLPE cables; test voltage; water tree; Cable insulation; Current measurement; Frequency domain analysis; Insulation testing; Length measurement; Performance evaluation; Polarization; Time measurement; Trees - insulation; Voltage;