This paper proposes a reliability evaluation method of various types of bus configurations in electrical substations. The reliability is evaluated by using Newton-Raphson power flow calculation with minimal cut sets. Two types of failure modes, i.e. active failure and passive failure, are considered. In addition, the operation of protective devices and power capacity of devices are also taken into account as they affect the path of power flow in substation. The reliability evaluation results of all bus configuration types in electrical substations are compared by the following indices; LOLF, LOLP, and EENS.
Keywords
Newton-Raphson method; load flow; power system faults; power system reliability; substation protection; EENS; LOLF; LOLP; Newton-Raphson power flow calculation; active failure; bus configuration types; electrical substations; failure modes; load growth consideration; minimal cut sets; passive failure; power capacity operation; protective devices operation; reliability evaluation method; Load flow; Load modeling; Power system reliability; Reliability engineering; Standards; Substations; Load Growth; Minimal cut set; Newton — Raphson Power Flow Calculation; Reliability Evaluation; Substation Configurations;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology (ECTI-CON), 2014 11th International Conference on
Conference_Location
Nakhon Ratchasima
Type
conf
DOI
10.1109/ECTICon.2014.6839853
Filename
6839853
Link To Document