• DocumentCode
    1620990
  • Title

    The arc-fault circuit protection

  • Author

    Parise, G. ; Martirano, L. ; Grasselli, U. ; Benetti, L.

  • Author_Institution
    Dept. of Electr. Eng., Rome Univ., Italy
  • Volume
    3
  • fYear
    2001
  • Firstpage
    1817
  • Abstract
    In electrical power systems bolted short-circuits are rare and the fault usually involves arcing and burning; mostly the limit value of minimum short-circuit depends on arcing-fault. In AC low voltage systems, the paper examines the arcing-fault branch circuits as weak points. Different protection measures are available against the arc-faults. A first measure that can guarantee a probabilistic protection is allowed by the adoption of overcurrent protective devices (OCPD), optimizing the design of the structure of the system and/or the coordination of protection. A well known complete protection is allowed by adopting arc-fault circuit interrupters (AFCI) for the protection of branch circuits. The authors suggest a new complete protection allowed wiring of the branch circuits, particularly including extension cords, with special power cables, protected by ordinary ground fault protective devices (GFPD). The suggested design for single-core or multi-core power cables is that each insulated core has a concentric conductor shield. Converting the line-to-line fault into a line to ground fault or into a mixed type is the goal of this special cable type faults ground-forced cable (FGFC).
  • Keywords
    arcs (electric); cable shielding; earthing; overcurrent protection; power cables; power system faults; power system protection; short-circuit currents; AC low voltage systems; arc-fault circuit interrupters; arc-fault circuit protection; arcing-fault; arcing-fault branch circuits; bolted short-circuits; branch circuits protection; burning; concentric conductor shield; extension cords; faults ground-forced cable; ground fault protective devices; insulated core; line to ground fault; line-to-line fault; minimum short-circuit limit value; multi-core power cables; overcurrent protective devices; power cables; power systems; probabilistic protection; protection coordination; protection measures; single-core power cables; weak points; Cable shielding; Circuit faults; Design optimization; Interrupters; Low voltage; Power cable insulation; Power cables; Power system faults; Power system measurements; Power system protection;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Conference, 2001. Thirty-Sixth IAS Annual Meeting. Conference Record of the 2001 IEEE
  • Conference_Location
    Chicago, IL, USA
  • ISSN
    0197-2618
  • Print_ISBN
    0-7803-7114-3
  • Type

    conf

  • DOI
    10.1109/IAS.2001.955778
  • Filename
    955778