Application of switchgear in unusual environments
Author :
Bowen, James E. ; Moore, Matthew C. ; Wactor, Michael W.
Author_Institution :
Dashiell Corp., Houston, TX, USA
fYear :
2010
Firstpage :
1
Lastpage :
10
Abstract :
With an increased emphasis on reducing the size of installations, switchgear designers are faced with the diametrically opposed requirements of increasing short-circuit withstand and continuous current ratings while reducing space for the air that provide both primary insulation and cooling for the energized parts. Using modern material science, compact integrated dielectric systems can be developed without compromising the essential features for achieving higher short-circuit withstand and continuous current ratings. As this trend continues, it is increasingly important for the user of the equipment to fully understand the implications of the operating environment. Humidity and contamination become increased risk factors for initiating partial discharge and tracking failures across the solid insulation system; reducing the mean time between failures and shortening the required maintenance cycles to unexpected levels. IEEE Standards define Usual Service Conditions for proper equipment installation and also offer application guidelines for Unusual Service Conditions. This paper will discuss these guidelines and define the owner and manufacturers´ responsibilities to assure system reliability by examining a specific installation and issues experienced.
Keywords :
failure analysis; insulation; maintenance engineering; partial discharges; short-circuit currents; switchgear; IEEE standards; compact integrated dielectric systems; equipment installation; maintenance cycles; manufacturer responsibility; mean time between failures; modern material science; partial discharge; short-circuit current; solid insulation system; switchgear; tracking failures; usual service condition; Dielectrics; Humidity; Insulation; Materials; Surface contamination; Switchgear; Unusual Service Conditions; Usual Service Conditions; environment; failure modes; switchgear;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Petroleum and Chemical Industry Conference (PCIC), 2010 Record of Conference Papers Industry Applications Society 57th Annual
Conference_Location :
San Antonio, TX
ISSN :
0090-3507
Print_ISBN :
978-1-4244-6800-3
Type :
conf
DOI :
10.1109/PCIC.2010.5666870
Filename :
5666870
Link To Document :
بازگشت