Abstract
Power grids are monitored by gathering data through remote sensors and estimating the state of the grid. Bad data detection schemes detect and remove poor data. False data is a special type of data injection designed to evade typical bad data detection schemes and compromise state estimates, possibly leading to improper control of the grid. Topology perturbation is a situational awareness method that implements the use of distributed flexible AC transmission system devices to alter impedance on optimally chosen lines, updating the grid topology and exposing the presence of false data. The success of the topology perturbation for improving grid control and exposing false data in AC state estimation is demonstrated. A technique is developed for identifying the false data injection attack vector and quantifying the compromised measurements. The proposed method provides successful false data detection and identification in IEEE 14, 24, and 39-bus test systems using AC state estimation.
Keywords
flexible AC transmission systems; power grids; power system state estimation; AC state estimation; bad data detection scheme; distributed flexible AC transmission system devices; false data injection attack vector; grid topology; optimized D-FACTS device placement; power grids; situational awareness method; topology perturbation; Jacobian matrices; Perturbation methods; Power grids; State estimation; Topology; Transmission line measurements; Vectors; Distributed Flexible AC Transmission Systems; Power Grids; Power System Security; Voltage Control;
fLanguage
English
Publisher
ieee
Conference_Titel
North American Power Symposium (NAPS), 2014
Conference_Location
Pullman, WA
Type
conf
DOI
10.1109/NAPS.2014.6965352
Filename
6965352
Link To Document