DocumentCode
1629290
Title
Local voltage instability monitoring and protection in the presence of self-restoring loads and two-level LTCs
Author
Lambrou, Charalambos ; Mandoulidis, Panagiotis ; Vournas, Costas
Author_Institution
Dept. of Electr. & Comput. Eng., Nat. Tech. Univ. of Athens, Athens, Greece
fYear
2011
Firstpage
1
Lastpage
9
Abstract
In this paper we give an overview of a local voltage instability monitoring and protection system integrated in the controller of each bulk power delivery LTC transformer. The proposed system identifies imminent voltage instability and subsequently applies corrective measures to restore stable operation by properly adjusting the distribution voltage setpoint of the LTC. The system is extended in this paper to include also the LTCs acting on EHV/HV autotransformers and is checked in the presence of self-restoring loads. Application on a small test system and a 52-bus test system shows the performance of the proposed system and the associated problems and solutions.
Keywords
autotransformers; on load tap changers; power system dynamic stability; power system protection; 52-bus test system; EHV-HV autotransformers; bulk power delivery LTC transformer; distribution voltage setpoint; local voltage instability monitoring; protection system; self-restoring loads; small-test system; two-level LTC; Generators; Monitoring; Power system stability; Stability analysis; Threshold voltage; Voltage control; Voltage measurement; Load Tap Changers; Voltage stability; protection against voltage collapse; restorative load; voltage instability monitoring;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Society General Meeting, 2011 IEEE
Conference_Location
San Diego, CA
ISSN
1944-9925
Print_ISBN
978-1-4577-1000-1
Electronic_ISBN
1944-9925
Type
conf
DOI
10.1109/PES.2011.6039524
Filename
6039524
Link To Document