DocumentCode
1632789
Title
Line current differential relay operation under severe current transformer saturation conditions
Author
Hedding, Roger A. ; Holst, Stig
Author_Institution
ABB Inc., Norwalk, CT
fYear
2009
Firstpage
256
Lastpage
262
Abstract
Relays rely on the current transformer to produce a secondary current that faithfully reflects the primary current for proper operation. In some instances this isn´t the case. This paper will look at cases where severe ct saturation can be a problem, review the real time digital simulator inputs to the relay, and look at what mechanisms in modern line current differential relays are used to mitigate the problem.
Keywords
power system faults; power system protection; relays; current transformer saturation; line current differential relay operation; real time digital simulator; Circuit faults; Current measurement; Current transformers; Digital relays; Power measurement; Power system protection; Power system relaying; Power transformers; Power transmission lines; Protective relaying;
fLanguage
English
Publisher
ieee
Conference_Titel
Protective Relay Engineers, 2009 62nd Annual Conference for
Conference_Location
Austin, TX
Print_ISBN
978-1-4244-4182-2
Electronic_ISBN
978-1-4244-4183-9
Type
conf
DOI
10.1109/CPRE.2009.4982517
Filename
4982517
Link To Document