DocumentCode :
1634931
Title :
How demand response from commercial buildings will provide the regulation needs of the grid
Author :
He Hao ; Middelkoop, Timothy ; Barooah, Prabir ; Meyn, Sean
Author_Institution :
Dept. of Mech. & Aerosp. Eng., Univ. of Florida, Gainesville, FL, USA
fYear :
2012
Firstpage :
1908
Lastpage :
1913
Abstract :
The statement “energy is not storable” is heard in energy conference lectures around the world, even though each person in the audience is sitting in a vast energy storage device. The heat storage in buildings is an enormous untapped resource for providing regulation services. This will be especially important as the grid is subject to more and more volatility from the introduction of power from renewable energy sources. This paper describes how regulation services can be obtained by exploiting the inherent flexibility of HVAC (Heating, Ventilation, Air Conditioning) systems in commercial buildings. A particular simulation test case is considered - A large commercial building at the University of Florida. The conclusions of this research demonstrate that, 1) A simplified model of the building that is adequate for control can be obtained from input-output measurements. In this study, the only control input considered is the supply fan power. 2) Control synthesis to regulate the building air temperature while simultaneously providing regulation to the grid can be cast as an LQR problem that admits a simple closed form solution. 3) Numerical experiments show that for this HVAC system, 15% of fan power capacity can be provided for regulation, while maintaining indoor temperature deviation to no more than ±0.2 °C. Based on these results, we conclude that the HVAC systems in 90, 000 medium-sized commercial buildings can provide the entire regulation service needed by PJM today, without any noticeable change in indoor air quality. The total regulation services that can be potentially provided by all the commercial buildings in the U.S. that have the necessary equipment in place are much higher. Our results indicate that supply fans in existing commercial buildings can provide about 70% of the current regulation capacity needed in the United States.
Keywords :
HVAC; buildings (structures); control system synthesis; power grids; power system control; temperature control; HVAC; building air temperature; control input; control synthesis; demand response; heating ventilation air conditioning systems; large commercial building; power grid; regulation service; renewable energy source; supply fan power; Atmospheric modeling; Buildings; Cooling; Power demand; Power measurement; Temperature measurement; Time measurement;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Communication, Control, and Computing (Allerton), 2012 50th Annual Allerton Conference on
Conference_Location :
Monticello, IL
Print_ISBN :
978-1-4673-4537-8
Type :
conf
DOI :
10.1109/Allerton.2012.6483455
Filename :
6483455
Link To Document :
بازگشت