DocumentCode
1637178
Title
Temperature influence on the anomalous breakdown phenomena in XLPE insulated cables
Author
Eish, Taher D.
Author_Institution
Dept. of Electr. Eng., Mansoura Univ., Egypt
fYear
1989
Firstpage
382
Lastpage
386
Abstract
The author reports results of investigations of the anomalous breakdown in XLPE (cross-linked polyethylene) insulated cables immersed in transformer oil under alternating (50 Hz) voltage when the temperature of the oil is increased. The study confirms that anomalous breakdown occurs in XLPE insulated power cables subjected to alternating voltages and that the breakdown voltage decreases as the insulation temperature increases. The distance of breakdown site from the high-voltage electrode decreases with increasing temperature up to 80°C. Above that value, the entire breakdown is of direct type; no anomalous breakdown occurs
Keywords
cable insulation; electric breakdown of solids; insulation testing; organic insulating materials; polymers; power cables; 50 Hz; 80 degC; XLPE insulated cables; anomalous breakdown; cross-linked polyethylene; insulation temperature; power cables; transformer oil; Breakdown voltage; Cable insulation; Electric breakdown; Electrodes; Oil insulation; Petroleum; Polyethylene; Power cables; Power transformer insulation; Temperature;
fLanguage
English
Publisher
ieee
Conference_Titel
Conduction and Breakdown in Solid Dielectrics, 1989., Proceedings of the 3rd International Conference on
Conference_Location
Trondheim
Type
conf
DOI
10.1109/ICSD.1989.69225
Filename
69225
Link To Document