Title :
The effect of using isolation transformers to supply small nonlinear loads
Author :
Costea, Marian ; Leonida, Tudor
Author_Institution :
Dept..of Electr. Power Syst., Politeh. Univ. of Bucharest, Bucharest, Romania
Abstract :
It is well known that between other non-linear loads the IT and office equipment or measuring equipment are important sources of current harmonics. There are particular cases when equipment of this type are supplied through isolation transformers such as equipment dedicated for interface between a high voltage laboratory and its control room or medical equipment. In the first step it was analyzed the influence of voltage level upon current harmonic content in the case of desktop computers and cathode ray tube monitors directly connected to the network. The main parameters were recorded using a professional power quality analyzer. The effect of an isolation transformer used to supply the same consumers was then evaluated. In particular situations, the use of isolation transformer diminishes the current harmonics injected in the supply network.
Keywords :
cathode-ray tube displays; harmonic distortion; harmonics suppression; power supply quality; transformers; cathode ray tube monitors; current harmonic content; desktop computers; harmonic mitigation; isolation transformers; nonlinear loads; power quality analyzer; Current measurement; Harmonic analysis; Monitoring; Power harmonic filters; Power transformer insulation; Voltage measurement; K-factor; derating; harmonic; isolation transformer; power quality; total harmonic distortion;
Conference_Titel :
Harmonics and Quality of Power (ICHQP), 2014 IEEE 16th International Conference on
Conference_Location :
Bucharest
DOI :
10.1109/ICHQP.2014.6842781